Lynx

Test up to 18,500 sq.ft. [1720 sq.m.]*
of duct at 4 in.wg. [1000 Pa]
Available in
115/1ph/60Hz (15 amp)
.

Standard Model:
inlet damper flow control
analog pressure gauges
set of 4 plates

Options:
.
digital gauges
low flow (1-10cfm) plate
dust cover
25 ft flex-duct

Cobra

Test up to 24,300 sq.ft. [2250 sq.m.]*
of duct at 4 in.wg. [1000 Pa]
Available in
115/1ph/60Hz (15 amp)
230/1ph/60Hz (8 amp)

Standard Model:
variable speed drive
digital pressure gauges
set of 4 plates

Options:
inlet damper flow control
analog gauges
low flow (1-10cfm) plate
dust cover
25 ft flex-duct

Panther

Test up to 49,000 sq.ft. [4550 sq.m.]*
of duct at 4 in.wg. [1000 Pa]
Available in
230v /1ph/60Hz (16 amp)
115v/1ph/60Hz (30 amp)

Standard Model:
variable speed drive
analog pressure gauges
set of 5 plates

Options:
115v/1ph/30 amp
digital gauges
low flow (1-10cfm) plate
dust cover
25 ft flex-duct

Rhino

Test up to 57,000 sq.ft. [5295 sq.m.]*
of duct at 4 in.wg. [1000 Pa]
Available in
230v/1ph/50-60Hz (21 amp)
230v/3ph/50-60Hz (13 amp)

Standard Model:
variable speed drive
analog pressure gauges
set of 6 plates

Options:
.
digital gauges
low flow (1-10cfm) plate
dust cover
25 ft flex-duct

Maximum Leakage Capacity (cfm)*
Model0.1 in.wg.1 in.wg.2 in.wg.4 in.wg.6 in.wg.7 in.wg.8 in.wg.9 in.wg.10 in.wg.12 in.wg.14 in.wg.16 in.wg.
Lynx570 cfm550 cfm540 cfm455 cfm290 cfm160 cfm
Cobra680 cfm650 cfm645 cfm600 cfm465 cfm405 cfm350 cfm250 cfm
Panther1400 cfm1350 cfm1320 cfm1210 cfm1065 cfm970 cfm875 cfm745 cfm615 cfm270 cfm
Rhino1700 cfm1630 cfm1550 cfm1420 cfm1330 cfm1255 cfm1185 cfm1110 cfm1035 cfm895 cfm660 cfm480 cfm

* – Using the largest size orifice plate with the tester. Use smaller orifices for smaller flow ranges; largest orifice for maximum flow range.